Detonation Flame Arrester - Group C & D Gases

Model 7758A

Detonation Flame Arrester - Group C & D Gases

The Groth Model 7758A Deflagration & Detonation Flame Arrester inhibits flame propagation in gas piping systems. The design makes it ideal to protect liquid storage tanks containing both NEC Group D and Group C vapors (IEC Class IIA and IIB1 through IIB3 vapors) with a Maximum Experimental Safe Gap (MESG) equal to or greater than 0.026" [0.65 mm].

Specifications

Size: 2" (DN50) x 4" (DN100) through 12" (DN300) x 30" (DN750)

Material: Housing standard material: carbon steel, stainless steel, aluminum • Flame element standard material: stainless steel

Pressure: Maximim Operational pressure 19.7 psia (1.36 bara)

Certification: Certified to ATEX Directive in compliance with EN ISO 16852:2010 Certificate #: IBExU12ATE X2170 X (Element Sizes 4”, 6”, 8” and 12” Unstable detonations) • Certified to ATEX Directive in compliance with EN ISO 16852:2010 Certificate #: IBExU12ATE X2171

Temperature: Operational Temperature Range -4 to 140 ºF (-20 to 60 ºC)

Features

• In-line or end-of-line deflagrations
• Stable detonations
• Unstable detonations (element sizes <=12”)
• Bi-directional with respect to flow and ignition source
• Wafer mesh element is standard
• Low pressure drop with multiple element sizes available for each flange size

 

Options

• Available in carbon steel, stainless steel, Alloy C276, and other materials
• Sensor ports
• Large inspection and cleaning ports
• Swing bolts for fast element removal
• Factory installed thermocouples for flame sensing

Dimensions

Detonation Flame Arrester - Group C & D Gases

Documents

Flame Control

Find out how we can help

Ready to improve the safety of your plant?
Sitemap

Request Info

Please let us know your first name.
Please let us know your company name.
Please let us know your email address.
Please let us know your Primary Phone Number.
Please let us know your message.
Please check the box above.